Watlow EZ-ZONE
®
PMI Controller • 132 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
A.Si
A.Si
Alarm (1 to 4)
Silencing
Turn silencing on to
allow the user to
disable this alarm.
oFF Off (62)
on On (63)
Off Instance 1
Map 1 Map 2
1490 1890
Offset to
next in-
stance (Map
1 equals
+50, for Map
2 equals
+60)
0x6D
(109)
1 to 4
6
29 9006 uint
RWES
A.dSP
A.dSP
Alarm (1 to 4)
Display
Display an alarm
message when an
alarm is active.
oFF Off (62)
on On (63)
On Instance 1
Map 1 Map 2
1510 1910
Offset to
next in-
stance (Map
1 equals
+50, for Map
2 equals
+60)
0x6D
(109)
1 to 4
0x10
(16)
30 9016 uint
RWES
A.dL
A.dL
Alarm (1 to 4)
Delay Time
Set the span of time
that the alarm will
be delayed after
the process value
exceeds the alarm
set point.
0 to 9,999 seconds 0 Instance 1
Map 1 Map 2
1520 1920
Offset to
next in-
stance (Map
1 equals
+50, for Map
2 equals
+60)
0x6D
(109)
1 to 4
0x15
(21)
31 9021 uint
RWES
a.CLr
A.Clr
Alarm (1 to 4)
Clear Alarm
Write to this reg-
ister to clear an
alarm
Note:
If an alarm is set-
up to latch when
active a.CLr will
appear on the dis-
play.
CLr Clear (0)
ignr Ignore (204)
- - - - Instance 1
Map 1 Map 2
1504 1904
Offset to
next in-
stance
(Map1 1
equals
+50, Map 2
equals +60)
0x6D
(109)
1 to 4
0xD
(13)
- - - - 9013 uint
W
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set