EasyManua.ls Logo

Watlow ez-zone pm - Limit Menu

Watlow ez-zone pm
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow EZ-ZONE
®
PMI Controller 114 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
Fi
Fi
Digital Input (5 to 6)
Function Instance
Select which Digital
Input will be trig-
gered by a true
state.
0 to 40 0 Instance 5
Map 1 Map 2
1326 1566
Offset to
next instance
(Map 1 & Map
2) equals +20
0x6E
(110)
5 to 6
4
139 10004 uint
RWES
Fi
Fi
Digital Input (7 to
12)
Function Instance
Select which Digital
Input will be trig-
gered by a true
state.
Note:
Modbus Map 1 has
instances 7 through
10 only
0 to 40 0 Instance 7
Map 1 Map 2
1406 1646
Offset to
next instance
(Map 1 & Map
2) equals +20
0x6E
(110)
7 to C
(12)
4
139 10004 uint
RWES
LiЛЏ
sEt
Limit Menu
L.sd
L.Sd
Limit (1)
Sides
Select which side or
sides of the process
value will be moni-
tored.
both Both (13)
high High (37)
LoФІ Low (53)
Both Instance 1
Map 1 Map 2
688 728
0x70
(112)
1
5
40 12005 uint
RWES
L.hy
L.hy
Limit (1)
Hysteresis
Set the hysteresis
for the limit func-
tion. This deter-
mines how far into
the safe range the
process value must
move before the
limit can be cleared.
0.001 to 9,999.000°F
or units
0.001 to 5,555.000°C
3.0°F or
units
2.0°C
Instance 1
Map 1 Map 2
682 722
0x70
(112)
1
2
41 12002 float
RWES
sp.Lh
SP.Lh
Limit (1)
Maximum Set Point
Set the high end of
the limit set point
range.
-1,999.000 to
9,999.000
9,999.000 Instance 1
Map 1 Map 2
696 736
0x70
(112)
1
9
42 12009 float
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set