Watlow EZ-ZONE
®
PMI Controller • 244 • Chapter 11 Appendix
PM Specifications
LineVoltage/Power (Minimum/Maximum Ratings)
• 85 to 264VÅ (ac), 47 to 63Hz
• 20 to 28VÅ (ac), 47 to 63Hz
• 12 to 40VÎ (dc)
• 14VA maximum power consumption (PM4, 8 & 9)
• 10VA maximum power consumption (PM6)
• Data retention upon power failure via non-volatile memory
• Compliant with SEMIF47-0200, Figure R1-1 voltage sag requirements @ 24VÅ (ac) or higher
Environment
• 0 to 149°F (-18 to 65°C) operating temperature
• -40 to 185°F (-40 to 85°C) storage temperature
• 0 to 90% RH, non-condensing
Accuracy
• Calibration accuracy and sensor conformity: ± 0.1% of span, ± 1°C @ the calibrated ambient
temperature and rated line voltage
• Types R, S, B; 0.2%
• Type T below -50°C; 0.2%
• Calibration ambient temperature @ 77 ± 5°F (25 ± 3°C)
• Accuracy span :1000 °F (540°C) min.
• Temperature stability: ±0.1 °F/°F (±0.1°C/°C) rise in ambient max.
Agency Approvals
• UL
®
Listed to UL 61010-1 File E185611
• UL
Reviewed to CSA C22.2 No.61010-1-04
• UL
50 Type 4X, NEMA 4X indoor locations, IP65 front panel seal (indoor use only)
• FM Class 3545 File 3029084 temperature limit switches
• CE-See Declaration of Conformity RoHS and W.E.E.E. complaint
• ODVA-EtherNet/IP™ and DeviceNet Compliance
• UL
Listed to ANSI/ISA 12.12.01-2007 File E184390
• This equipment is suitable for use in Class 1, Div.2, Groups A, B, C and D or non-hazardous
locations only. Temperature Code T4A
• UL
reviewed to Standard No. CSA C22.2 No.213-M1987, Canadian Hazardous locations
• All models, CSA C22.2 No. 24 File 158031 Class 4813-02, CSA Approved
Controller
• User selectable heat/cool, on-off, P, PI, PD, PID or alarm action, not valid for limit control-
lers
• Auto-tune with TRU-TUNE
®
+ adaptive control algorithm
• Control sampling rates: input = 10Hz, outputs = 10Hz