Watlow EZ-ZONE
®
PMI Controller 109 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
fn
Fn
Digital Output (5 to
12)
Function
Select what func-
tion will drive this
output.
Note:
Modbus Map 1
has instances 5
through 8 only
off Off (62)
aLЛЏ Alarm (6)
hEat Heat (36)
CooL Cool (20)
sof.1 Special Func-
tion Output 1 (1532)
sof.2 Special Func-
tion Output 2 (1533)
tE.o1 Timer Event
Output 1 (1951)
tE.o2 Timer Event
Output 2 (1952)
tE.o3 Timer Event
Output 3 (1953)
Ent.a Profile Event
Out A (233)
Ent.b Profile Event
Out B (234)
h.Er Heater Error
(184)
Off Instance 5
Map 1 Map 2
1008 1128
Offset to
next instance
(Map 1 & Map
2) equals +30
0x 6A
(106)
5 to 12
5
83 6005 uint
RWES
fi
Fi
Digital Output (5 to
12)
Output Function
Instance
Set the instance
of the function se-
lected above.
Note:
Modbus Map 1
has instances 5
through 8 only
1 to 4 1 Instance 5
Map 1 Map 2
1010 1130
Offset to
next instance
(Map 1 & Map
2) equals +30
0x6A
(106)
5 to 12
6
84 6006 uint
RWES
o.Ct
o.Ct
Digital Output (5 to
12)
Time Base Type
Set the time base
type. This param-
eter is only used
with PID control,
but can be set any-
time.
Note:
Modbus Map 1
has instances 5
through 8 only
ftb Fixed Time Base
(34)
vtb Variable Time
Base (103)
Fixed
Time
Base
Instance 5
Map 1 Map 2
1002 1122
Offset to
next instance
(Map 1 & Map
2) equals +30
0x6A
(106)
5 to 12
2
85 6002 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.