Watlow EZ-ZONE
®
PMI Controller • 110 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
o.tb
o.tb
Digital Output (5 to
12)
Fixed Time Base
Set the time base
for fixed-time-base
control.
Note:
Modbus Map 1
has instances 5
through 8 only
0.1 to 60.0 seconds 1.0 Instance 5
Map 1 Map 2
1004 1124
Offset to
next instance
(Map 1 & Map
2) equals +30
0x6A
(106)
5 to 12
3
86 6003 float
RWES
o.Lo
o.Lo
Digital Output (5 to
12)
Low Power Scale
The power output
will never be less
than the value
specified and will
represent the value
at which output
scaling begins.
0.0 to 100.0% 0.0 Instance 5
Map 1 Map 2
1016 1136
Offset to
next instance
(Map 1 & Map
2) equals +30
0x6A
(106)
5 to 12
9
87 6009 float
RWES
o.hi
o.hi
Digital Output (5 to
12)
High Power Scale
The power output
will never be great-
er than the value
specified and will
represent the value
at which output
scaling stops.
0.0 to 100.0% 100.0 Instance 5
Map 1 Map 2
1018 1138
Offset to
next instance
(Map 1 & Map
2) equals +30
0x6A
(106)
5 to 12
A (10)
88 6010 float
RWES
LEu
LEv
Digital Input (5 to 6)
Active Level
Select which action
will be interpreted
as a true state.
high High (37)
LoФІ Low (53)
High Instance 5
Map 1 Map 2
1320 1560
Offset to
next instance
(Map 1 & Map
2) equals +20
0x6E
(110)
5 to 6
1
137 10001 uint
RW
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set