Watlow EZ-ZONE
®
PMI Controller • 165 • Chapter 7 Profiling Page
Profiling Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pa-
ram-
eter
ID
Data
Type
and
Access
**
JS
JS
Step Type Parameters
Jump Step
When Step Type is Jump,
this specifies which step to
jump back to. Jump Step
must be a lower step num-
ber than the current step
number.
1 to 40
0 Instance 1
Map 1 Map 2
2592 4522
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
0xC (12)
21012 uint
RWE
JC
JC
Step Type Parameters
Jump Count
When Step Type is Jump,
this specifies the number of
jumps to repeat. A value
of 0 creates an infinite loop.
Loops can be nested four
deep.
0 to 9,999
0 Instance 1
Map 1 Map 2
2594 4524
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
0xD (13)
21013 uint
RWE
End
End
Step Type Parameters
End Type
When Step Type is End, this
specifies what the control-
ler will do when this profile
ends.
oFF Control Mode
set to Off (62)
Hold Hold last
closed-loop set
point in the profile
(47)
USEr User, reverts
to previous set
point (100)
Off Instance 1
Map 1 Map
2
2596 4526
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
0xE (14)
21014 uint
RWE
Ent1
Ent1
Step Type Parameters
Event 1
When Step Type is not Un-
used Step, select whether
Event Output 1 or 2 is on or
off during this step.
oFF Off (62)
on On (63)
Off Instance 1
Map 1 Map
2
2582 4512
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
7
21007 uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other inter-
faces.
** R: Read, W: Write, E: EEPROM, S: User Set