Watlow EZ-ZONE
®
PMI Controller • 172 • Chapter 8 Factory Page
Factory Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
SLoC
SLoC
Security Setting
Write Security
Set the write se-
curity clearance
level. The user
can access the
selected level
and all lower
levels.
If the Set Lockout
Security level is
higher than the
Read Lockout Se-
curity, the Read
Locko
ut Security
level takes pri-
ority.
0 to 5 5
Instance 1
Map 1 Map 2
1844 2314
0x67
(103)
1
0x0B
(11)
- - - - 3011
uint
RWE
LoC.L
LoC.L
Security Setting
Locked Access
Level
Determines user
level menu vis-
ibility when
Password Enable
is set to on. See
Features section
under Password
Security.
1 to 5 5
- - - - - - - - - - - - 3016
uint
RWE
roLL
roLL
Security Setting
Rolling Password
When power is
cycled a new
Public Key will
be displayed and
User Password
changes.
off
Off
on
On
Off
- - - - - - - - - - - - 3019
uint
RWE
pas.u
PAS.u
Security Setting
User Password
Used to acquire
access to menus
made available
through the
Locked Access
Level setting.
10 to 999 63
- - - - - - - - - - - - 3017
uint
RWE
** R: Read, W: Write, E: EEPROM, S: User Set