Watlow EZ-ZONE
®
PMI Controller 207 Chapter 9 Features
3. Press the Advance Key until Lock Operations prompt LoC.o appears in the bottom display.
4. Press the Up Key ¿ to change the default value from 2 to 3.
5. Press the Advance Key again and change the Lock Profiling prompt LoC.p appears in the
bottom display.
6. Press the Down Key ¯ to change the default value from 3 to 2.
7. Press the Advance Key until Read Lock rLoC appears in the bottom display.
8. Press the Down Key ¯ to change the default value from 5 to 2.
9. Press the Advance Key until Set Lock sLo C appears in the bottom display.
10. Press the Down Key ¯ to change the default value from 5 to 4.
With the above settings, the Home Page and the Proling Page can be accessed, and all writ-
able parameters can be written to. Due to the Read lock setting of 2, all pages with security
levels greater than 2 will be locked out (inaccessible).
Another example of Method 1 lockout usage could be that an operator wants read access to
all pages while allowing read/write access to the Home Page and the Lockout Menu only. To
setup this scenario follow the steps below:
1. From the Home Page, press and hold the Innity Key ˆ and the Advance Key for ap-
proximately six seconds. CUst will appear in the upper display and fCty will appear in the
lower display.
2. Press the Up Key ¿ until LoC appears in the upper display and fCty will appear in the
lower display.
3. Press the Advance Key until Read Lock rLoC appears in the bottom display and change it
to 5.
4. Press the Advance Key until Set Lock SLoC appears in the bottom display and change it to
1.
Although the Factory Page is always visible, some menus within it can be restricted.
Lockout Security
sLoC
and
rLoC
Factory Page Menus
Menus
Security Level
0 1 2 3 4 5
Custom Menu
N N N N N Y
Lockout Menu*
Y Y Y Y Y Y
Diagnostic
Menu**
N Y Y Y Y Y
Calibration Menu
N N N N N Y
* Using lockout Method 1 with SLoC set to 0, all writable parameters within the control
will be inhibited (not writable) with two exceptions, SLoC and rLoC. As shown below,
both of these parameters can always be seen and modified.
** Diagnostic Menu and all associated prompts are always visible and never writable