Watlow EZ-ZONE
®
PMI Controller • 40 • Chapter 2 Install and Wire
Warning:
ç
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may
result in damage to equipment
and property, and/or injury or
loss of life.
Note:
Maximum wire size termination
and torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination
or two 1.31 mm
2
(16 AWG)
• 0.56 Nm (5.0 in-lb.) torque
Note:
Adjacent terminals may be la-
beled differently, depending on
the model number
.
Note:
To prevent damage to the con-
troller, do not connect wires to
unused terminals.
Note:
Maintain electrical isolation
between digital input-outputs,
switched dc/open collector
outputs and process outputs to
prevent ground loops.
Note:
This equipment is suitable for
use in CLASS I, DIVISION 2,
Groups A, B, C and D or Non-
Hazardous locations only. Tem-
perature Code T4
Warning:
ç
Explosion Hazard – Substitution
of component may impair suit-
ability for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not dis-
connect while the circuit is live
or unless the area is known to be
free of ignitable concentrations
of flammable substances.
Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical relay,
solid state relay or open collector
output options requires use of an
R.C. suppressor.
Output 1, 3 Mechanical Relay, Form C
normally open
normally closed
common
L_
K_
J_
Slot A, B
• 5A at 240VÅ (ac) or
30VÎ (dc) maximum
resistive load
• 20mA at 24V minimum
load
• 125VA pilot duty at
120/240VÅ (ac), 25VA
at 24VÅ (ac)
• 100,000 cycles at rated
load
• Output does not supply
power.
• For use with ac or dc
Output 1: (L1,K1,J1)
PM _ _ _ [E] _ - _ _ _ _
_ _ _
Output 3: (L3,K3,J3)
PM _ _ _ _ _ - _ _ [E] _
_ _ _
normally open
common
normally closed
L
_
K
_
J
_
Output 1, 3 Universal Process
volts or current -
current +
volts +
F_
G_
H_
Slot A, B
• 0 to 20mA into 800
Ω maximum load
• 0 to 10VÎ (dc) into 1
kΩ minimum load
• Scalable
• Output supplies pow-
er
• Cannot use voltage
and current outputs
at same time
• Output may be used
as retransmit or con-
trol.
Output 1: (F1,G1,H1)
PM _ _ _ [F] _ - _ _ _ _
_ _ _
Output 3: (F3,G3,H3)
PM _ _ _ _ _ - _ _ [F] _
_ _ _
negative
volts +
current +
4 to 20 mA
0 to 10 V
F
3
G
3
H3