Watlow PM PLUS™ 6     •  116  •  Chapter 10 Appendix
Reversed    Range limiting only
RTD
S1 open       Yes, pulled up.
S2 open       Not implemented.
S3 open       Yes, pulled up.
S1 short to S2     Yes, pulled up
S1 short to S3     Yes, pulled down to under range.
S2 shorted to S3    Not implemented, Possible, monitor S2 voltage.
S1 and S2 open    Yes, pulled down to under range.
S1 and S3 open    Yes, S1 pulled up.
S2 and S3 open    Yes pulled up.
Thermistor
S1 open       Yes, pulled up to sensor over range.
S3 open       Yes, pulled up to sensor over range.
S1 short to S3     Yes, pulled down to sensor under range.
S1 and S3 open    Yes, S1 pulled up to sensor over range.