Controller
User-selectable heat/cool, on-off, P, PI, PD, PID or alarm action
Auto-tune with TRU-TUNE+ adaptive control algorithm
Control sampling rates: input = 10Hz, outputs = 10Hz
Profile Ramp/Soak
4 profiles, 40 total steps
Accuracy (typical): ±30 PPM at 77°F (25°C) +30/-100 PPM at -4 to 149°F (-20 to 65°C)
Isolated Serial Communications
EIA 232/485, Modbus
®
RTU
EtherNet/IP™/Modbus
®
TCP
DeviceNet™
PROFIBUS DP
SAE J1939 CAN bus
Wiring Termination—Touch-Safe Terminals
Input, power and controller output terminals are touch safe, removable, 12 to 22 AWG
Universal Input
Thermocouple, grounded or ungrounded sensors greater than 20MΩ input impedance, 3µA open sensor detection,
2kΩ source resistance max.
RTD 2- or 3-wire, platinum, 100Ω and 1000Ω @ 32°F (0°C) calibration to DIN curve (0.00385 Ω/Ω/°C)
Process, 0-20mA @ 100Ω, or 0-10VDC @ 20kΩ, 0-50mV at 20MΩ, 0-1000Ω potentiometer; scalable; inverse scal-
ing
Functional Operating Range
Type J: -346 to 2192°F (-210 to 1200°C)
Type K: -454 to 2500°F (-270 to 1371°C)
Type T: -454 to 750°F (-270 to 400°C)
Type E: -454 to 1832°F (-270 to 1000°C)
Type N: -454 to 2372°F (-270 to 1300°C)
Type C: 32 to 4200°F (0 to 2315°C)
Type D: 32 to 4200°F (0 to 2315°C)
Type F: 32 to 2449°F (0 to 1343°C)
Type R: -58 to 3214°F (-50 to 1767°C)
Type S: -58 to 3214°F (-50 to 1767°C)
Type B: 32 to 3300°F (0 to 1816°C)
RTD (DIN): -328 to 1472°F (-200 to 800°C)
Process: -1999 to 9999 units