Watlow PM PLUS™ 6 • 133 • Chapter 10 Appendix
Operator Interface
• LCD display
• Smooth touch keypad
• Programmable function key
Line Voltage/Power
• High voltage option: 85 to 264VAC, 47 to 63Hz
• Low voltage option: 20 to 28VAC, +10/-15%; 50/60Hz, ±5% or 12 to 40VDC
• Max. power consumption: 10VA
Environment
• Operating temperature: 0 to 149°F (-18 to 65°C)
• Storage temperature: -40 to 185°F (-40 to 85°C)
• Relative humidity: 0 to 90% RH, non-condensing
Agency Approvals
• cULus
®
UL
®
/EN/CSA C22.2 No 61010-1 Listed, File E185611
• CSA C22.2 No. 24, File 158031 (1/32 and 1/16 DIN sizes) all models are approved.
• IP 67, UL
®
Type 4X front seal indoor locations
• cULus
®
ANSI/ISA 12.12.01-2012, CSA-C22.2 No. 213-1987, Class 1,
Div. 2, Groups A, B, C and D, Temperature Code T4A,
File E184390 (optional)
• FM Class 3545 (limit controls)
• CE, RoHS by design, W.E.E.E.
• EtherNet/IP™ and DeviceNet™ ODVA Conformance Tested displays