Watlow PM PLUS™ 6 • 41 • Chapter 4: Operations
Default Operations Parameters/Sublists
The default parameters in the Operations List vary on every PM PLUS. This list is populated with
parameters applicable to the features enabled on the device and the settings chosen in
Operations
— Setup. (Refer to the configuration code on the device's product label).
Parameter Description Range Default ID
Seconds Set the timer period seconds. 0 to 59 10 31027
Special Output Function
These appear in Operations on devices with a V in the 12th digit of the configuration code.
Source Value A Special Output Function (1)
View the value of Source A.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
- - - -
35007
Source Value B Special Output Function (1)
View the value of Source B.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
- - - -
35008
Output Value 1 Special Output Function (1)
View the value of this function's Output 1.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
- - - -
35010
Output Value 2 Special Output Function (1)
View the value of this function's Output 2.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
- - - -
35012
Profile Functions
These appear in Operations on devices with N or R in the 4th digit of the configuration code.
See Operations - Setup - for a full list of configurable parameters for this functionality
Profile Start Starts the profile 1 to 40 1 22001
Profile Action
Request
Requests any of the range of actions None (61)
Step (89)
End (148)
Resume (147)
Pause (146)
Profile (77)
None 22011
Profile Status Currently running step in the profile 1 to 40 ---- 22004