CHAPTER 7 - DIAGNOSTICS AND TROUBLESHOOTING
Note:
(1) In case of E04 Fault due to inverter overtemperature, allow the
inverter to cool down before trying to reset it.
NOTE!
The faults act as follows:
E00 to E06: switches off the relay that has been programmed to
“no fault”, disables the PWM pulses, displays the fault code on the
display. Some data are saved on the EEPROM memory: keypad
reference and EP (electronic potentiometer) (when the function
“backup of the references” at P120 has been enabled), the occurred
fault number, the status of the integrator of the I x t function
(overcurrent).
E24: Indicates the fault code on the LED display.
E08, E09, E31 and E41: do not allow inverter operation (it is not
possible to enable the inverter); the fault code is indicated on the
LED display.
FAULT RESET
(1)
POSSIBLE CAUSES
E04 Power-on Ambient temperature too high (> 50 ºC), (> 40 °C for the
Inverter Manual (key ) 15.2 Amodel) and/or output current too high.
Overtemperature Auto-reset Blocked or defective fan.
DI NOTE
The heat sink overtemperature protection(E04) is activated
when the heat sink temperature (P008) reaches 103 ºC
or 133 ºC for the 15.2 A model.
E05 P156 set too low for the motor that is being used.
Overload Motor is under an actual overload condition.
at output
I x t Function
E06 Wiring at DI1 to DI4 inputs is open [not connected to
External Error GND (pin 5 of the XC1 control connector)].
(digital input progra
for ext.fault is open)
E08 Electrical noise.
CPU Error
E09 Contact WEG Memory with corrupted values.
Program Memory (refer to section 7.3)
Error (Checksum)
E24 It is automatically reset Incompatible parameters were programmed
Programming when the incompatible Refer to table 5.1.
error parameters are changed
E31 Contact WEG Inverter control circuit is defective.
Keypad (HMI) Servicing Electrical noise in the installation (electromagnetic
Connection Fault (Refer to section 7.3) interference).
E41 Contact WEG Servicing Inverter power circuit is defective.
Self- Diagnosis (refer to section 7.3)
Fault