Fault
3066501_201910 WOLF GmbH | 67
Fault
code
Message Cause Remedy
24 Speed fault
Fan
Set fan speed is not achieved. Press reset button.
Switch power supply OFF/ON.
Check power cable to fan.
Check fan.
26 Fan fault The fan does not stop. Check power cable to fan.
Check fan.
Press reset button.
27 Faulty stratication
sensor
Faulty stratication cylinder
sensor or lead.
Check sensor.
Check lead.
29 Differential pressure
sensor short circuit
Differential pressure sensor
or cable defective.
Test sensor.
Check lead.
Press reset button.
30 CRC
Burner control unit
The EEPROM data set is invalid. Switch power supply OFF/ON.
If fault persists:
change burner control units.
34 CRC BCC-ID incorrect
in CM-EEPROM
Boiler coding card fault. Replace boiler coding card.
35 BCC not correct Boiler coding card has been
removed or incorrectly inserted.
Ret the correct boiler coding
card.
36 CRC BCC-ID incorrect
in the BCC
Boiler coding card fault. Replace boiler coding card.
37 Incorrect BCC The boiler coding card is
incompatible with the burner
control unit.
Insert the correct boiler coding
card.
Press reset button.
38 BCC update required Boiler coding card fault, PCB
requires a new boiler coding card
(if replacement part).
Reinsert boiler coding card.
Check boiler coding card.
39 BCC system error Boiler coding card fault Replace boiler coding card.
42 Condensate pump not
pumping
Condensate pump is defective.
Drain line is blocked.
No power supply to the
condensate pump.
Check the condensate pump.
Check drain line.
Check power connector and
fuses.
52 max. cylinder heating
time
The cylinder heat time lasts longer
than permitted.
Check DHW sensor (cylinder
sensor) and sensor lead.
Vent cylinder.
Extend cylinder heating time.
Press reset button.
78 Header sensor fault Faulty header sensor or lead. Check sensor.
Check lead.
85 Relay test Relay test failed. Switch power supply OFF/ON.
Press reset button.
90 BCU communication Emergency stop via ChipCom.
Communication between control
unit PCB and burner control unit
disrupted.
Press reset button.
Check connection between
burner control unit and HCM-2
board.
91 Bus communication Duplicated eBus address. Assign the eBus address once.
95 Prog. mode Burner control unit is controlled
by PC.
No action.
96 Reset Reset button pressed too many
times.
Switch power supply OFF/ON.
99 System error
Burner control unit
Internal burner control unit fault. Switch power supply OFF/ON.