Fault
3066501_201910 WOLF GmbH | 67
Fault
code
Message Cause Remedy
24 Speed fault
Fan
– Set fan speed is not achieved. ► Press reset button.
► Switch power supply OFF/ON.
► Check power cable to fan.
► Check fan.
26 Fan fault – The fan does not stop. ► Check power cable to fan.
► Check fan.
► Press reset button.
27 Faulty stratication
sensor
– Faulty stratication cylinder
sensor or lead.
► Check sensor.
► Check lead.
29 Differential pressure
sensor short circuit
– Differential pressure sensor
or cable defective.
► Test sensor.
► Check lead.
► Press reset button.
30 CRC
Burner control unit
– The EEPROM data set is invalid. ► Switch power supply OFF/ON.
If fault persists:
► change burner control units.
34 CRC BCC-ID incorrect
in CM-EEPROM
– Boiler coding card fault. ► Replace boiler coding card.
35 BCC not correct – Boiler coding card has been
removed or incorrectly inserted.
► Ret the correct boiler coding
card.
36 CRC BCC-ID incorrect
in the BCC
– Boiler coding card fault. ► Replace boiler coding card.
37 Incorrect BCC – The boiler coding card is
incompatible with the burner
control unit.
► Insert the correct boiler coding
card.
► Press reset button.
38 BCC update required – Boiler coding card fault, PCB
requires a new boiler coding card
(if replacement part).
► Reinsert boiler coding card.
► Check boiler coding card.
39 BCC system error – Boiler coding card fault ► Replace boiler coding card.
42 Condensate pump not
pumping
– Condensate pump is defective.
– Drain line is blocked.
– No power supply to the
condensate pump.
► Check the condensate pump.
► Check drain line.
► Check power connector and
fuses.
52 max. cylinder heating
time
– The cylinder heat time lasts longer
than permitted.
► Check DHW sensor (cylinder
sensor) and sensor lead.
► Vent cylinder.
► Extend cylinder heating time.
Press reset button.
78 Header sensor fault – Faulty header sensor or lead. ► Check sensor.
► Check lead.
85 Relay test – Relay test failed. ► Switch power supply OFF/ON.
► Press reset button.
90 BCU communication – Emergency stop via ChipCom.
– Communication between control
unit PCB and burner control unit
disrupted.
► Press reset button.
► Check connection between
burner control unit and HCM-2
board.
91 Bus communication – Duplicated eBus address. ► Assign the eBus address once.
95 Prog. mode – Burner control unit is controlled
by PC.
No action.
96 Reset – Reset button pressed too many
times.
► Switch power supply OFF/ON.
99 System error
Burner control unit
– Internal burner control unit fault. ► Switch power supply OFF/ON.