EasyManua.ls Logo

Wolf COB-2 - Common Fault Diagnosis

Wolf COB-2
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fault
66 | WOLF GmbH 3066501_201910
Fault
code
Message Cause Remedy
4 No ame When the burner starts, no ame
forms by the end of safety time.
Ignition electrodes contaminated.
Air in the oil feed line.
Heat generator contaminated.
Check oil line, check oil level,
if necessary.
Check ignition electrodes and
ignition transformer.
Check solenoid valve for oil
pump.
Check that the condensate
can drain off freely.
Press reset button.
Check CO
2
values.
Service the equipment.
5 Flame failure Flame failure during operation.
Flue gas return system (ue gas
in the supply air).
Air in the oil feed line.
Heat generator contaminated.
Check ue system for leaks.
Check oil line, check oil level,
if necessary.
Press reset button.
Check CO
2
values.
Service the equipment.
6 Temperature limiter,
excess temperature
The ow has exceeded the limit of
the temperature limiter (95°C).
Vent the system.
Check the heating circuit
pump.
7 Flue gas sensor,
excess temperature
The ue gas temperature has
exceeded 120°C.
Clean the heating water heat
exchanger.
Check that all displacement
devices are properly installed.
Check the ow through the
heat generator.
Check that the heating ow
and return are connected
correctly.
Press reset button.
8 Flue gas/supply air
damper does not
respond
Flue gas/supply air damper
contact (E1) fails to close or open
when there is a demand.
Check wiring of ue gas/supply
air damper.
11 False ame A ame is recognised before the
burner starts.
Check solenoid valve for oil
pump.
Check ignition electrodes and
ignition transformer.
Press reset button.
12 Boiler sensor faulty Faulty boiler sensor or lead. Check sensor.
Check lead.
13 Flue gas sensor faulty Faulty ue gas sensor or lead. Check sensor.
Check lead.
14 Faulty cylinder sensor
CS
Faulty cylinder sensor or lead. Check sensor.
Check lead.
15 Outside temperature
sensor fault
Faulty outside temperature sensor
or lead.
Check sensor.
Check lead.
22 Differential pressure
sensor not responding
Supply air or ue gas path
blocked.
Differential pressure too low in
pre-purge phase.
Differential pressure sensor or
cable defective.
Air ducts not connected or
incorrectly connected.
Check supply air and ue gas
path.
Check differential pressure
sensor.
Check lead.
Check air ducts.
23 Differential
pressure sensor not
deactivating
Differential pressure sensor fails
to switch back.
Inltrating air owing through the
heat generator.
Check differential pressure
sensor.

Table of Contents

Related product manuals