Page 154/174 © Woodward
MUX
No.
Contents (words)
Unit Note
19/1 58
External alarm 1
Bit 15 = 1 \
Bit 14 = 1 /
Discrete input [D01]
Note – On double /fourfold bits the follow-
ing is valid: If the indicated bit combination
is fulfilled (
high byte and low byte) ,the
message is active (otherwise inactive).
Bit 13 = 1 \
Bit 12 = 1 /
Discrete input [D02]
Bit 11 = 1 \
Bit 10 = 1 /
Discrete input [D03]
Bit 9 = 1 \
Bit 8 = 1 /
Discrete input [D04]
Bit 7 = 1 \
Bit 6 = 1 /
Discrete input [D05]
Bit 5 = 1 \
Bit 4 = 1 /
Discrete input [D06]
Bit 3 = 1 \
Bit 2 = 1 /
Discrete input [D07]
Bit 1 = 1 \
Bit 0 = 1 /
Discrete input [D08]
19/2 59
External alarm 2
Bit 15 = 1 \
Bit 14 = 1 /
Discrete input [D09]
Note – On double /fourfold bits the follow-
ing is valid: If the indicated bit combination
is fulfilled (
high byte and low byte) ,the
message is active (otherwise inactive).
Bit 13 = 1 \
Bit 12 = 1 /
Discrete input [D10]
Bit 11 = 1 \
Bit 10 = 1 /
Discrete input [D11]
Bit 9 = 1 \
Bit 8 = 1 /
Discrete input [D12]
Bit 7 = 1 \
Bit 6 = 1 /
Discrete input [D13]
Bit 5 = 1 \
Bit 4 = 1 /
Discrete input [D14]
Bit 3 = 1 \
Bit 2 = 1 /
Discrete input [D15]
Bit 1 = 1 \
Bit 0 = 1 /
Discrete input [D16]
19/3 60
Internal alarm 7 Bit 15 = 1 --Internal--
Bit 14 = 1 --Internal--
Note – On double /fourfold bits the follow-
ing is valid: If the indicated bit combination
is fulfilled (
high byte and low byte) ,the
message is active (otherwise inactive).
Bit 13 = 1 --Internal--
Bit 12 = 1 --Internal--
Bit 11 = 1 --Internal--
Bit 10 = 1 --Internal--
Bit 9 = 1 --Internal--
Bit 8 = 1 --Internal--
Bit 7 = 1 MCB close malfunction
Bit 6 = 1 GCB close malfunction
Bit 5 = 1 --Internal--
Bit 4 = 1 --Internal--
Bit 3 = 1 --Internal--
Bit 2 = 1 --Internal--
Bit 1 = 1 --Internal--
Bit 0 = 1 Immediate stop
20/1 61
Analog input [T1] The measured value is transmitted.
20/2 62
Analog input [T2] The measured value is transmitted.
20/3 63
Analog input [T3] The measured value is transmitted.
21/1 64
Analog input [T4] The measured value is transmitted.
21/2 65
Analog input [T5] The measured value is transmitted.
21/3 66
Analog input [T6] The measured value is transmitted.
22/1 67
Analog input [T7] The measured value is transmitted.

Table of Contents

Other manuals for Woodward GCP-30 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Woodward GCP-30 Series and is the answer not in the manual?

Woodward GCP-30 Series Specifications

General IconGeneral
BrandWoodward
ModelGCP-30 Series
CategoryController
LanguageEnglish

Related product manuals