Manual 37278B GCP-30 Series - Genset Control
Page 168/174 © Woodward
Parameter Setting range Default value Customer setting
ENGINE CONFIGURATION
Configure engine
YES/NO NO Y N Y N
L
Aux.services prerun
0 to 999 s 0 s
L
Aux.services postrun
0 to 999 s 0 s
L
Start-stop-logic for
DIESEL
GAS
EXTERNAL [EXT]
DIESEL DIESEL
GAS
EXT
DIESEL
GAS
EXT
L
Min.speed for ignit.
0 to 999 rpm 100 rpm
Gas
Ignition delay
0 to 99 s 3 s
.. L
Gasvalve delay
0 to 99 s 5 s
..
Max. attempts to start
1 to 6 3
..
Starter time
2 to 99 s 10 s
..
Start pause time
1 to 99 s 8 s
.. L
f lower before start
ON/OFF OFF on off on off
Gas L
time f lower bef.start
0 to 999 s 5 s
Diesel
Preglow time
0 to 99 s 3 s
..
Max. attempts to Start
1 to 6 3
..
Starter time
2 to 99 s 10 s
..
Start pause time
1 to 99 s 5 s
L..
f lower before start
ON/OFF OFF on off on off
L..
time f lower bef.start
0 to 999 s 5 s
Diesel L
Fuel relay logic
Open to stop [OPEN]
Close to stop [STOP]
Open to stop OPEN
STOP
OPEN
STOP
Cool down time
0 to 999 s 15 s
Delayed engine monitoring
1 to 99 s 8 s
Firing speed reached f>
5 to 70 Hz 15 Hz
Pickup input
ON/OFF ON on off on off
Number of pickup teeth
30 to 280 160
L
Gen.rated speed
0 to 3,000 rpm 1,500 rpm
COUNTER CONFIGURATION
Configure counters
YES/NO NO Y N Y N
Service interval in
0 to 9,999 h 300 h
Set oper.hours counter
0 to 65,000 h 0 h
Set start counter
0 to 32,000 0
kWh counter set in
kWh
MWh
kWh kWh
MWH
kWh
MWH
kWh counter set
0 to 65,500 kWh/MWh 0 kWh
Time
00:00 to 23:59 00:00
Year,month
00 to 99,01 to 12 00,00
Day/weekday
01 to 31/1 to 7 00,0
RPQ
Timer on at 00:00
00:00 to 23:59 00:00
RPQ
Timer off at 00:00
00:00 to 23:59 00:00
RPQ
Week M S days NNNNNNN
Y(es)/N(o) NNNNNNN
RPQ This parameter is only available in the RPQ Package and may only be accessed via LeoPC1 depending on the unit
B+X This parameter is only available in the B+X Packages and may only be accessed via LeoPC1 depending on the unit
L This parameter may only be accessed via LeoPC1 depending on the unit