Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 97/174
Parameter 192
Gen.overcurrent
limit 2 000%
Independent time overcurrent, threshold value, limit 2 0 to 300 %
If this threshold value has been exceeded for at least the delay time (Para-
meter 193), the following alarm class is initiated.
Issuing of class F3 alarm
Parameter 193
Gen.overcurrent
delay 2 00.00s
Independent time overcurrent, delay, limit 2 0.02 to 9.98 s
For the control unit to recognize a time-overcurrent fault condition, the threshold
value configured in Parameter 192) must be exceeded without interruption for this
peri
od of time.
Parameter 194
Gen.overcurrent
Cool down ON
Open GCB with coasting due to overcurrent ON/OFF
ON ................ If the GCB is opened due to an overcurrent fault condition, an engine
cool-down is performed prior to engine stop.
OFF .............. The engine is stopped without a cool-down.