2.7 H: Terminal Functions
182 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Table 2.27 Contact output Terminal Settings
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Figure 2. 51
Figure 2.51 During Run Time Chart
Setting Function Page Setting Function Page
0 During Run 182 1C Motor 2 Selection 189
1 Zero Speed 183 1D During Regeneration 189
2 Speed Agree 1 183 1E Restart Enabled 189
3 User-Set Speed Agree 1 184 1F Motor Overload Alarm (oL1) 189
4 Frequency Detection 1 184 20 IGBT Overheat Pre-Alarm (oH) 189
5 Frequency Detection 2 185 21 User-Set Alarm 189
6 Drive Ready 185 22 Mechanical Weakening Detection (N.O.) 189
7 DC Bus Undervoltage 185 2F Maintenance Period 189
8 During Baseblock (N.O.) 185 30 During Torque Limit 189
9 Frequency Reference Source 185 31 During Speed Limit 190
A Run Command Source 186 32 During Speed Limit in Torque Control 190
B Torque Detection 1 (N.O.) 186 37 During Frequency Output 190
C Frequency Reference Loss 186 38 Drive Enabled 190
EFault 186 39 Watt Hour Pulse Output 190
F Through Mode 186
3A
Cooling Fan, Transformer Abnormal
Temperature Rise
190
10 Minor Fault 186 3C LOCAL/REMOTE Status 190
11 Fault Reset Command Active 186 3D During Speed Search 190
12 Timer Output 186 3E PID Feedback Low 190
13 Speed Agree 2 186 3F PID Feedback High 191
14 User-set Speed Agree 2 187 40
Close Command for Commercial Power Supply
Side Breaker
191
15 Frequency Detection 3 187 41
Close Command for Drive Secondary Side
Breaker
191
16 Frequency Detection 4 188 42 Completion Signal for Synchronous Transfer 191
17 Torque Detection 1 (N.C.) 186 4C During Fast Stop 191
18 Torque Detection 2 (N.O.) 186 4D oH Pre-Alarm Time Limit 191
19 Torque Detection 2 (N.C.) 186 60 Drive Cooling Fan Alarm 191
1A During Reverse 188 62 Inrush Current Suppression Circuit Fault 191
1B During Baseblock (N.C.) 189 100 to 160 Function 0 to 60 with Inverse Output 191
Status Description
Open Drive is stopped.
Closed A Run command is input or the drive is during deceleration or during DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
MV1000ParameterGuide_E_conditional.book 182 ページ 2013年10月11日 金曜日 午後8時18分