9.9 F: Options
612 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-05
(03E9)
Subnet Mask 1 Sets the first octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
255
(0 - 255)
256
F7-06
(03EA)
Subnet Mask 2 Sets the second octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
255
(0 - 255)
256
F7-07
(03EB)
Subnet Mask 3 Sets the third octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
255
(0 - 255)
256
F7-08
(03EC)
Subnet Mask 4 Sets the fourth octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
0
(0 - 255)
257
F7-09
(03ED)
Gateway Address 1 Sets the first octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
192
(0 - 255)
257
F7-10
(03EE)
Gateway Address 2 Sets the second octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
168
(0 - 255)
257
F7-11
(03EF)
Gateway Address 3 Sets the third octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
1
(0 - 255)
257
F7-12
(03F0)
Gateway Address 4 Sets the fourth octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
1
(0 - 255)
257
F7-13
(03F1)
Address Mode at Startup Sets the method to set option card IP addresses.
0 : Static
1 : BOOTP
2 : DHCP
Note:
• The following setting values are available when using the PROFINET
communication option card (SI-EP3).
–0: Static
–2: DHCP
• When F7-13 = 0, set parameters F7-01 to F7-12 [IPAddress 1 to Gateway Address
4] to set the IP Address. Be sure to set a different IP address for each drive on the
network.
2
(0 - 2)
257
F7-14
(03F2)
Duplex Mode Selection Sets the duplex mode setting method.
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
4 : Half/Full
5 : Auto/Half
6 : Auto/Full
7 : Full/Half
8 : Full/Auto
1
(0 - 8)
258
F7-15
(03F3)
Communication Speed
Selection
Sets the communications speed.
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
10
(10, 100 - 102)
258
F7-16
(03F4)
Timeout Value Sets the detection time for a communications timeout.
Note:
Set this parameter to 0.0 to disable the connection timeout function.
0.0 s
(0.0 - 30.0 s)
258
F7-17
(03F5)
EtherNet/IP Speed
Scaling Factor
Sets the scaling factor for the speed monitor in the EtherNet/IP Class ID 2AH Object. 0
(-15 - +15)
259
F7-18
(03F6)
EtherNet/IP Current Scale
Factor
Sets the scaling factor for the output current monitor in the EtherNet/IP Class ID 2AH
Object.
0
(-15 - +15)
259
F7-19
(03F7)
EtherNet/IP Torque Scale
Factor
Sets the scaling factor for the torque monitor in the EtherNet/IP Class ID 2AH Object. 0
(-15 - +15)
259