Parameter List
9
9.10 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 631
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H5-20
(0B57)
Communication
Parameters Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
0
(0, 1)
310
H5-22
(11CF)
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of
15DFH).
0 : Disabled
1 : Enabled
0
(0, 1)
311
H5-23
(158D)
BACnet Max Master Sets the maximum number of master MAC ID to scan to when the drive polls for the next
node (Poll for Master).
7F
(1 - 7F)
311
H5-24
(3DA0)
BACnet Max Info Frames Sets the maximum number of information frames for BACnet. 3
(1 - 255)
311
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0044H (U1-05)
(0000H - FFFFH)
311
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0045H (U1-06)
(0000H - FFFFH)
311
H5-27
(158B)
RUN
Function 5A Register 3
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0042H (U1-03)
(0000H - FFFFH)
311
H5-28
(158C)
RUN
Function 5A Register 4
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0049H (U1-10)
(0000H - FFFFH)
311
H5-33
(3FB3)
Power-up CALL Alarm Enables and disables CALL [Serial Comm Transmission Error] alarm detection.
0 : Disabled
1 : Enabled
1
(0, 1)
312
H5-34
(3FB4)
RUN
Comm Error (CE) Go-To-
Frequency
Sets the speed at which the drive will run when H5-04 = 4 [Communication Error Stop
Method = Run at H5-34] and there is a CE.
0.0 Hz
(0.0 - 400.0 Hz)
312
H5-35
(3FB5)
RUN
Comm Error (CE) Go-To-
Timeout
When H5-04 = 4 [Communication Error Stop Method = Run at H5-34] and a CE is
present, the drive will run at the H5-34 [Comm Error (CE) Go-To-Frequency] speed for
this length of time before it triggers a CE fault.
Note:
Set this parameter to 0 s to disable the time-out.
0 s
(0 - 6000 s)
312
H5-36
(3FB6)
CE Fault Restart Select Sets the drive to restart (L5-01 [Number of Auto-Restart Attempts]) after a CE fault.
0 : No Retry
1 : Retry
0
(0, 1)
312
H7: Virtual MFIO selection
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H7-00
(116F)
Expert
Virtual MFIO selection Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to
operate the virtual I/O function.
0 : Disabled
1 : Enabled
0
(0, 1)
313
H7-01
(1185)
Expert
Virtual Multi-Function
Input 1
Sets the function that enters the virtual input set in H7-10 [Virtual Multi-Function Output
1].
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not
available.
F
(1 - 1B8)
313
H7-02
(1186)
Expert
Virtual Multi-Function
Input 2
Sets the function that enters the virtual input set in H7-12 [Virtual Multi-Function Output
2].
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not
available.
F
(1 - 1B8)
313

Table of Contents