A.2 Parameter Table
330 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
20 to
2F
External Fault
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue
running)
2D: N.C., Always Detected, Alarm Only (continue
running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
OOO150
30 PID Integral Reset Closed: Resets the PID control integral value. O O O 151
31 PID Integral Hold Closed: Maintains the current PID control integral value. O O O 151
32 Multi-Step Speed Reference 4 Used to select Multi-Step Speeds set in d1-01 to d1-16 O O O 151
34 PID Soft Starter Closed: Disables the PID soft starter b5-17. O O O 151
35 PID Input Switch Closed: Inverses the PID input signal O O O 151
40
Forward Run Command
(2-wire sequence)
Open: Stop
Closed: Forward run
Note: Can not be set together with Settings 42 or 43.
OOO151
41
Reverse Run Command (2-wire
sequence)
Open: Stop
Closed: Reverse run
Note: Can not be set together with Settings 42 or 43.
OOO151
42
Run Command (2-wire
sequence 2)
Open: Stop
Closed: Run
Note: Can not be set together with Settings 40 or 41.
OOO152
43
FWD/REV Command (2-wire
sequence 2)
Open: Forward
Closed: Reverse
Note: Can not be set together with Settings 40 or 41.
OOO152
44 Offset Frequency 1 Addition Closed: Adds d7-01 to the frequency reference. O O O 152
45 Offset Frequency 2 Addition Closed: Adds d7-02 to the frequency reference. O O O 152
46 Offset Frequency 3 Addition Closed: Adds d7-03 to the frequency reference. O O O 152
60
DC Injection Braking
Command
Closed: Triggers DC Injection Braking (b2-02) O O - 152
H1 Multi-Function Digital Input Selections
H1-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
PM

Table of Contents