A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 329
Parameter List
A
7 Accel/Decel Time 1 Used to switch between Accel/Decel. Time 1/2 O O O 142
8 Baseblock Command (N.O.)
Open: Normal operation
Closed: No drive output
OOO142
9 Baseblock Command (N.C.)
Open: No drive output
Closed: Normal operation
OOO142
A Accel/Decel Ramp Hold
Closed: The drive pauses during acceleration or
deceleration and maintains the output frequency.
OOO143
B Drive Overheat Alarm (OH2) Closed: Displays an OH2 alarm O O O 144
C Terminal A2 Enable
Open: Terminal A2 disabled
Closed: Terminal A2 enabled
OOO144
F Not used
Select this setting when not using the terminal or when
using the terminal in a pass-through mode.
OOO144
10 Up Command Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency
reference.
Ensure that the increase and decrease commands are set in
conjunction with one another. The frequency reference
source must be set to operator (b1-01 = 0).
OOO144
11 Down Command O O O 144
12 Forward Jog Closed: Runs forward at the Jog Frequency d1-17. O O O 146
13 Reverse Jog Closed: Runs reverse at the Jog Frequency d1-17. O O O 146
14 Fault Reset
Closed: Resets faults if the cause is cleared and the Run
command is removed.
OOO147
15 Fast-Stop (N.O.)
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run
must be cycled.
OOO147
16 Motor 2 Selection
Open: Motor 1 (E1-, E2-)
Closed: Motor 2 (E3-, E4-)
OOO148
17 Fast-stop (N.C.) Open: Decelerates according to C1-09 (Fast-stop Time) O O O 147
18 Timer Function Input
Set the timer delay using parameters b4-01 and b4-02.
Ensure this function is set in conjunction with the multi-
function output timer (H2- = 12).
OOO148
19 PID Disable Closed: PID control disabled O O O 148
1A Accel/Decel Time Selection 2 Switches Accel/Decel times. O O O 149
1B Program Lockout
Open: Parameters can not be edited. (except U1-01 if
reference source is set for operator)
Closed: Parameters may be edited and saved.
OOO149
1E Reference Sample Hold
Closed: Samples the analog frequency reference and
operates the drive at that speed.
OOO149
H1 Multi-Function Digital Input Selections
H1-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
PM