A.2 Parameter Table
328 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
H1: Multi-Function Digital Input
H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".
H1-01
Multi-Function Digital Input Terminal S1
Function Selection
Assigns a function to the
multi-function digital inputs.
Refer to “Multi-Function
Digital Input Selection
Table” for a description of
setting values.
1 to 9F
<40>
40 A A A 438 139
H1-02
Multi-Function Digital Input Terminal S2
Function Selection
41 A A A 439 139
H1-03
Multi-Function Digital Input Terminal S3
Function Selection
24 A A A 400 139
H1-04
Multi-Function Digital Input Terminal S4
Function Selection
14 A A A 401 139
H1-05
Multi-Function Digital Input Terminal S5
Function Selection
3(0)
<18>
<18> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.
<40> The availability of certain functions depends on the control method used.
AAA 402 139
H1-06
Multi-Function Digital Input Terminal S6
Function Selection
4(3
)
<18
>
A A A 403 139
H1 Multi-Function Digital Input Selections
H1-
Setting
Function Description
Control
Mode
Pg.
V/f
OL
V
PM
0 3-Wire Sequence
Closed: Reverse rotation (only if the drive is set up for 3-
wire sequence)
OOO140
1 LOCAL/REMOTE Selection
Open: REMOTE, Reference 1 or 2 (b1-01/02 or b1-15/
16)
Closed: LOCAL, LED operator is run and reference
source
OOO141
2 External Reference 1/2
Open: Run and frequency reference source 1 (b1-01/02)
Closed: Run and frequency reference source 2 (b1-15/16)
OOO142
3 Multi-Step Speed Reference 1
Used to select Multi-Step Speeds set in d1-01 to d1-16
OOO142
4 Multi-Step Speed Reference 2 O O O 142
5 Multi-Step Speed Reference 3 O O O 142
6 Jog Reference Selection
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority
over all other reference sources.
OOO142