A.2 Parameter Table
332 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
H2: Multi-Function Digital Outputs
Use H2 parameters to assign functions to the multi-function digital outputs.
H2-01
Terminal MA, MB and MC
Function Selection (relay)
Refer to “Multi-Function Digital
Output Selection Table” for a
description of setting values.
0 to 192
<40>
<40> The availability of certain functions depends on the control method used.
E A A A 40B 157
H2-02
Terminal P1 Function Selection
(open-collector)
0 A A A 40C 157
H2-03
Terminal P2 Function Selection
(open-collector)
2AAA40D157
H2-06 Watt Hour Output Unit Selection
Determines the unit for the watt
hour output signal (H2- = 39).
If a digital output is set to this
function, a 200 ms pulse signal is
output when the what hour counter
increases according to the unit
selected. Intended to drive a counter,
meter or PLC for logging kWh.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
0 to 4 0 A A A 437 172
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description
Control
Mode
Pg.
V/f
O
LV
P
M
0 During Run Closed: A Run command is active or voltage is output. O O O 158
1 Zero Speed Closed: Output frequency is 0. O O O 159
2 Speed Agree 1
Closed: Output frequency equals the speed reference (plus or minus
the hysteresis set to L4-02).
OOO159
3 User Set Speed Agree 1
Closed: Output frequency and speed reference equal the value in
L4-01 (plus or minus the hysteresis of L4-02).
OOO160
4 Frequency Detection 1
Closed: Output frequency is less than or equal to the value in L4-01
with hysteresis determined by L4-02.
OOO161
5 Frequency Detection 2
Closed: Output frequency is greater than or equal to the value in
L4-01, with hysteresis determined by L4-02.
OOO162