7 Utility Functions (Fn)
7-12
7.6 Initializing Parameter Settings (Fn005)
This function is used when returning to the factory settings after changing parameter settings.
Follow the steps below to initialize the parameter setting.
• Be sure to initialize the parameter settings while the servo ON (/S_ON) signal is OFF.
• After initialization, turn OFF the power supply and then turn ON again to validate the
settings.
Step
Display after
Operation
Keys Operation
1
Press the MODE/SET Key to select the utility function
mode.
2 Press the UP or DOWN Key to select Fn005.
3
Press the DATA/SHIFT Key for approximately one second.
The display shown on the left appears.
Note: When "no-oP" blinks for approximately one second,
the write prohibited setting is set in Fn010. Change
the setting in Fn010, and press the key again after
enabling writing. (Refer to 7.12.)
4
Display blinks
Press the MODE/SET Key. Then, the parameters will be
initialized.
During initialization, the display shown on the left blinks.
5
Display blinks
When the initialization of parameter setting completes, the
display shown on the left blinks for about one second.
6
The display changes from "donE" to the display shown on
the left.
7
Press the DATA/SHIFT Key for approximately one second.
"Fn005" is displayed again.
8 Turn OFF the power and then turn ON again to validate the setting.
MODE