No. Name Description
H1-03 Multi-Function Digital Input Terminal S3 Function Selection Selects function of terminal S3
H1-04 Multi-Function Digital Input Terminal S4 Function Selection Selects function of terminal S4
H1-05 Multi-Function Digital Input Terminal S5 Function Selection Selects function of terminal S5
H1-06 Multi-Function Digital Input Terminal S6 Function Selection Selects function of terminal S6
H1-07 Multi-Function Digital Input Terminal S7 Function Selection Selects function of terminal S7
H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function Description
0 3-Wire Sequence Closed: Reverse rotation (only for 3-wire sequence)
1 Local/Remote Selection
Open: Remote, Reference 1 or 2 (b1-01/02 or b1-15/16)
Closed: Local, LED operator is run and reference source
2 External Reference 1/2
Open: Run and frequency reference source 1 (b1-01/02)
Closed: Run and frequency reference source 2 (b1-01/02)
3 Multi-Step Speed Reference 1
Used to select Multi-Step Speeds set in d1-01 to d1-164 Multi-Step Speed Reference 2
5 Multi-Step Speed Reference 3
6 Jog Reference Selection
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority over all other
reference sources.
7 Accel/Decel Time 1 Used to switch between Accel/Decel. Time 1/2
8 Baseblock Command (N.O.)
Open: Normal operation
Closed: No drive output
9 Baseblock Command (N.C.)
Open: No drive output
Closed: Normal operation
A Accel/Decel Ramp Hold
Closed: The drive pauses during acceleration or deceleration and maintains
the output frequency.
B Drive Overheat Alarm (oH2) Closed: Displays an oH2 alarm
C Terminal A1/A2 Enable
Terminal status differs depending on drive software version.
PRG: 1016 and later:
Open: Analog input selected by H3-14 is disabled.
Closed: Analog input selected by H3-14 is enabled.
PRG: 1015 and earlier:
Open: Analog inputs selected for terminals A1 and A2 are disabled.
Closed: Analog inputs selected for terminals A1 and A2 are enabled.
F Not used
Select this setting when not using the terminal or when using the terminal
in a pass-through mode.
10 Up Command
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference
11 Down Command
12 Forward Jog Closed: Runs forward at the Jog Frequency d1-17.
13 Reverse Jog Closed: Runs reverse at the Jog Frequency d1-17.