158 Parameters
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 191). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 20
Reserved 21…23
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 24
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 25
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 26
Other [bit] Source selection (see Terms and abbreviations on page 100). -
22.23 Constant speed
sel2
When bit 0 of parameter 22.21 Constant speed function is 0
(Separate), selects a source that activates constant speed 2.
When bit 0 of parameter 22.21 Constant speed function is 1
(Packed), this parameter and parameters 22.22 Constant
speed sel1 and 22.24 Constant speed sel3 select three
sources that are used to activate constant speeds. See table
at parameter 22.22 Constant speed sel1.
For the selections, see parameter 22.22 Constant speed sel1.
Not selected
22.24 Constant speed
sel3
When bit 0 of parameter 22.21 Constant speed function is 0
(Separate), selects a source that activates constant speed 3.
When bit 0 of parameter
22.21 Constant speed function is 1
(Packed), this parameter and parameters 22.22 Constant
speed sel1 and 22.23 Constant speed sel2 select three
sources that are used to activate constant speeds. See table
at parameter 22.22 Constant speed sel1.
For the selections, see parameter 22.22 Constant speed sel1.
Not selected
22.26 Constant speed 1 Defines constant speed 1 (the speed the motor will turn when
constant speed 1 is selected).
300.00 rpm;
360.00 rpm
(95.20 b0)
-30000.00
30000.00 rpm
Constant speed 1. See par.
46.01
22.27 Constant speed 2 Defines constant speed 2. 600.00 rpm;
720.00 rpm
(95.20 b0)
-30000.00
30000.00 rpm
Constant speed 2. See par.
46.01
22.28 Constant speed 3 Defines constant speed 3. 900.00 rpm;
1080.00 rpm
(95.20 b0)
-30000.00
30000.00 rpm
Constant speed 3. See par.
46.01
22.29 Constant speed 4 Defines constant speed 4. 1200.00 rpm;
1440.00 rpm
(95.20 b0)
-30000.00
30000.00 rpm
Constant speed 4. See par.
46.01
No. Name/Value Description Def/FbEq16