212 Parameters
37.19 ULC frequency
table point 4
Defines the fourth frequency point.
See parameter 37.16 ULC frequency table point 1.
50.0 Hz
-500.0…500.0 Hz Frequency. 1 = 1 Hz
37.20 ULC frequency
table point 5
Defines the fifth frequency point.
See parameter 37.16 ULC frequency table point 1.
60.0 Hz
-500.0…500.0 Hz Frequency. 1 = 1 Hz
37.21 ULC underload
point 1
Defines the first of the five points on the Y-axis that together
with the corresponding point on the X-axis (37.11 ULC speed
table point 137.15 ULC speed table point 5 or 37.15 ULC
speed table point 537.20 ULC frequency table point 5)
define the underload (lower) curve.
Each point of the underload curve must have a lower value
than the corresponding overload point.
10.0%
-1600.0…1600.0% Underload point. 1 = 1%
37.22 ULC underload
point 2
Defines the second underload point.
See parameter 37.21 ULC underload point 1.
15.0%
-1600.0…1600.0% Underload point. 1 = 1%
37.23 ULC underload
point 3
Defines the third underload point.
See parameter 37.21 ULC underload point 1
25.0%
-1600.0…1600.0% Underload point. 1 = 1%
37.24 ULC underload
point 4
Defines the fourth underload point.
See parameter 37.21 ULC underload point 1
30.0%
-1600.0…1600.0% Underload point. 1 = 1%
37.25 ULC underload
point 5
Defines the fifth underload point.
See parameter 37.21 ULC underload point 1
30.0%
-1600.0…1600.0% Underload point. 1 = 1%
37.31 ULC overload point
1
Defines the first of the five points on the Y-axis that together
with the corresponding point on the X-axis (37.11 ULC speed
table point 137.15 ULC speed table point 5 or 37.15 ULC
speed table point 5
37.20 ULC frequency table point 5)
define the overload (higher) curve.
Each point of the overload curve must have a higher value
than the corresponding underload point.
300.0%
-1600.0…1600.0% Overload point. 1 = 1%
37.32 ULC overload point
2
Defines the second overload point.
See parameter 37.31 ULC overload point 1.
300.0%
-1600.0…1600.0% Overload point. 1 = 1%
37.33 ULC overload point
3
Defines the third overload point.
See parameter 37.31 ULC overload point 1.
300.0%
-1600.0…1600.0% Overload point. 1 = 1%
37.34 ULC overload point
4
Defines the fourth overload point.
See parameter 37.31 ULC overload point 1.
300.0%
-1600.0…1600.0% Overload point. 1 = 1%
37.35 ULC overload point
5
Defines the fifth overload point.
See parameter 37.31 ULC overload point 1.
300.0%
-1600.0…1600.0% Overload point. 1 = 1%
No. Name/Value Description Def/FbEq16