Parameters 265
High High priority pump.
The IPC system prefers high priority pump.
Normal Normal priority pump.
Low Low priority pump.
The low priority pump runs as little as possible. It is started
only when the demand requires full pumping capacity.
76.81 PFC 1 interlock Defines if the PFC motor 1 can be started. An interlocked
PFC motor cannot be started.
0 = Interlocked (not available), 1 = Available.
Available.
PFC motor is
available
Interlocked. PFC
motor is not in use
PFC motor is interlocked and not available. 0
Available. PFC
motor is available
PFC motor is available. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 8
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 191). 9
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 10
Other [bit] Source selection (see Terms and abbreviations on page 100). -
76.82 PFC 2 interlock See parameter 76.81 PFC 1 interlock. Available.
PFC motor is
available
76.83 PFC 3 interlock See parameter 76.81 PFC 1 interlock. Available.
PFC motor is
available
76.84 PFC 4 interlock See parameter 76.81 PFC 1 interlock. Available.
PFC motor is
available
76.85 PFC 5 interlock See parameter
76.81 PFC 1 interlock. Available.
PFC motor is
available
76.86 PFC 6 interlock See parameter 76.81 PFC 1 interlock. Available.
PFC motor is
available
76.90 LC low level switch Selects the source for digital low level switch. Selected
Not selected Low level switch is inactive. 0
Selected Low level switch is active. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
No. Name/Value Description Def/FbEq16