266 Parameters
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 8
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 9
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 10
Other [bit] Source selection (see Terms and abbreviations on page 100). -
76.91 LC high level switch Selects the source for digital high level switch. Selected
Not selected High level switch is inactive. 0
Selected High level switch is active. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 8
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 9
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 10
Other [bit] Source selection (see Terms and abbreviations on page 100). -
76.92 LC low level action Selects the action for drive to indicate when digital low level
switch is activated.
See parameter 76.90 LC low level switch (page 265).
Warning
No action Low level switch is disabled and does not generate any event. 0
Warning Low level switch generates 0xD509
Low level warning. 1
Fault Low level switch generates 0xD403 Low level fault. 2
76.93 LC high level action Selects the action for drive to indicate when digital high level
switch is activated.
See parameter 76.91 LC high level switch (page 266).
Warning
No action High level switch is disabled and does not generate any
event.
0
Warning High level switch generates 0xD508 High level warning. 1
Fault High level switch generates 0xD402 High level fault. 2
76.95 Regulator bypass
control
Defines if direct-on-line pumps are automatically started and
stopped.
This setting can be used in applications with a low number of
sensors and low accuracy requirements.
Disable
Disable Automatic starting and stopping is disabled. 0
Enable Automatic starting and stopping is enabled. 1
Other [bit] Source selection (see Terms and abbreviations on page 100). -
76.101 IPC parameter
synchronization
Defines parameter synchronization in IPC system. Enable
Enable Parameter synchronization is enabled.
Disable Parameter synchronization is disabled.
76.102 IPC synchronization
settings
Selects the settings that are synchronized between drives in
inverter-to-inverter communication bus.
The process PID and IPC parameters are synchronized.
Note: This parameter does not synchronize AI parameters.
0b0110
No. Name/Value Description Def/FbEq16