Parameters 271
PQ curve The PQ curve is used for flow calculation.
You can configure pressure sensor settings with parameter
group 81 Sensor settings.
The figure below shows the PQ performance curve of the
pump for the flow calculation function.
101
80.14 Flow feedback
multiplier
Defines the multiplier (k) used with the flow calculation The
output value of 80.13 Flow feedback function is multiplied by
this value.
1.00
-200000.00…
200000.00
Multiplier. 1 = 1
80.15 Maximum flow Defines the nominal maximum flow of the system. This value
is used to calculate the actual flow percentage value so that
the value 100% for 80.02 corresponds to the value of this
parameter.
1000.00
-200000.00…
200000.00
Sets the limit for maximum flow protection. 1 = 1
80.16 Minimum flow Defines the nominal minimum flow of the system. 1.00
-200000.00...
200000.00 m
3
/h
Sets the limit for minimum flow protection. 1 = 1 m
3
/h
80.17 Maximum flow
protection
Selects the action for maximum flow protection function. No action
No action Maximum flow protection is disabled. 0
Warning Generates D50C Maximum flow protection warning. 1
Fault Generates D406 Maximum flow protection fault. 2
Speed ref safe Speed reference safe is activated. 3
80.18 Minimum flow
protection
Selects the action for minimum flow protection function. No action
No action Minimum flow protection is disabled. 0
Warning Generates D50D Minimum flow protection warning. 1
Fault Generates D407 Minimum flow protection fault. 2
Speed ref safe Speed reference safe is activated. 3
80.19 Flow check delay Defines the time after motor start when the flow protection is
active.
5.00
0.00...3600.00 s Flow check delay. 1 = 1 s
80.22 Pump inlet diameter Defines the pump inlet pipe diameter. 0.100
0.010...
32767.000 cm
Pump inlet pipe diameter. 1 = 1 cm
No. Name/Value Description Def/FbEq16
P [kW] or P [hp]
Q [m
3
/h] or
Q [gpm]
2
4
5
3
1