278 Parameters
Triggered Cleaning sequence is triggered by parameter 83.11 specifies
warning generation only.
4
83.02 Pump cleaning
progress
Displays the pump cleaning progress. 0.0
0.0...100.0% Percentage 10 = 1%
83.03 Total cleaning count Displays the total cleaning count. 0
0...1000000 Total cleaning count. 1 = 1
83.10 Pump cleaning
action
Enables the pump cleaning action. Cleaning
Off Pump cleaning is disabled. 0
Cleaning Pump cleaning is started based on triggers. 1
Warning only Generates warning message based on triggers. 2
83.11 Pump cleaning
triggers
Enables/disables the pump cleaning sequence for the drive,
and defines the triggering conditions.
Note: If DI1 remains On after cleaning is finished, no cleaning
sequence is started. The drive starts cleaning on next start, if
the trigger signal is On when motor is started.
0b0000
83.12 Manually force
cleaning
Starts pump cleaning. Not active
Not active Pump cleaning is not active. 0
Start cleaning now Starts pump cleaning immediately. 1
DI4 Starts pump cleaning when DI4 goes high. 2
DI5 Starts pump cleaning when DI5 goes high. 3
DI4 Starts pump cleaning when DI6 goes high. 4
Other [bit] Source selection (see Terms and abbreviations on page 100). -
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Reserved
1 Every start Cleaning starts at every start.
2 Every stop Cleaning starts at every stop.
3 Reserved
4 Overload detection Cleaning sequence starts when overload situation is
detected. To set up the overload curve, see parameters in
group 37 User load curve.
5 Underload detection Cleaning sequence starts when underload situation is
detected. To set up the overload curve, see parameters in
group 37 User load curve.
6 Fixed time interval Time interval defined by parameter 83.15 Fixed time interval.
7 Combined timer1 Combined timer 1 of timed functions starts cleaning.
8...9 Reserved
10 Supervision 1 Cleaning sequence starts when Supervision 1 is high.
11 Supervision 2 Cleaning sequence starts when Supervision 2 is high.
12 Supervision 3 Cleaning sequence starts when Supervision 3 is high.
13 DI4 Cleaning sequence starts when DI4 is high.
14 DI5 Cleaning sequence starts when DI5 is high.
15 DI6 Cleaning sequence starts when DI6 is high.