Parameters 279
83.15 Fixed time interval Defines the constant time interval between cleaning cycles.
This parameter is used only when cleaning is triggered by
time interval.
02:00:00h
00:00:00...45:12:15
h
Time 1 = 1h
83.16 Cycles in cleaning
program
Defines the number of cycles performed in cleaning program.
For example, 1 cycle = 1 forward + 1 reverse step.
3
1...65535 Value range
83.20 Cleaning speed
step
Defines the speed/frequency step size in pump cleaning.
Cleaning speed step is same for positive and negative
directions.
Note: If you have disabled the negative rotation direction by
speed limits, the pump cleaning does not operate in the
negative direction.
80
0...100% Percentage of the cleaning speed/frequency value. 1 = 1%
83.25 Time to cleaning
speed
Defines the time required for the drive to reach cleaning
speed set by parameter 83.20 Cleaning speed step.
3.000
0.000...60.000 s Time 1 = 1s
83.26 Time to zero-speed Defines the time required for the drive to reach zero speed
from the cleaning speed set by parameter 83.20 Cleaning
speed step.
3.000
0.000...60.000 s Time 1 = 1s
83.27 Cleaning on time Defines the cleaning On time when the drive is running at
cleaning speed set by parameter 83.20 Cleaning speed step.
10.000
0.000...1000.000 s Time 1 = 1s
83.28 Cleaning off time Defines the cleaning Off time when the drive stays at zero
speed between positive and negative pulses and after one
cleaning cycle before starting a new cleaning cycle.
5.000
0.000...1000.000 s Time 1 = 1s
83.35 Cleaning count fault Activates the cleaning count monitoring, and selects the
action it takes if it detects too many cleaning starts within the
time defined by parameter 83.36 Cleaning count time.
See section Cleaning count monitoring (page 56).
No action
No action No action 0
Warning Warning 1
Fault Fault 2
83.36 Cleaning count time Defines the time for cleaning count monitoring.
See section Cleaning count monitoring (page 56).
00:01:00h
00:00:00...45:12:15
h
Time 1 = 1h
83.37 Maximum cleaning
count
Defines the maximum cleaning counts allowed.
See section Cleaning count monitoring (page 56).
5
0...30 Maximum cleaning counts. 1 = 1
No. Name/Value Description Def/FbEq16