EasyManua.ls Logo

ABB ACS550 - Page 183

ABB ACS550
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS550 User’s Manual 183
Parameters
3 = DI3 – Enables the Interlocks function and assigns a digital input (starting with DI3) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
the number of PFC relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFC)]
the Autochange function status (disabled if 8118
AUTOCHNG INTERV = 0, and otherwise enabled).
4 =
DI4 – Enables the Interlock function and assigns a digital input (starting with DI4) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
the number of PFC relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFC)]
the Autochange function status (disabled if 8118
AUTOCHNG INTERV = 0, and otherwise enabled).
Code Description
No. PFC
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI1…DI2: Free
DI3: Speed Reg Motor
DI4…DI6: Free
Not allowed
1
DI1…DI2: Free
DI3: Speed Reg Motor
DI4: First PFC Relay
DI5…DI6: Free
DI1…DI2: Free
DI3: First PFC Relay
DI4…DI6: Free
2
DI1…DI2: Free
DI3: Speed Reg Motor
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Free
DI1…DI2: Free
DI3: First PFC Relay
DI4: Second PFC Relay
DI5…DI6: Free
3
DI1…DI2: Free
DI3: Speed Reg Motor
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Third PFC Relay
DI1…DI2: Free
DI3: First PFC Relay
DI4: Second PFC Relay
DI5: Third PFC Relay
DI6: Free
4 Not allowed
DI1…DI2: Free
DI3: First PFC Relay
DI4: Second PFC Relay
DI5: Third PFC Relay
DI6: Fourth PFC Relay
5…6 Not allowed Not allowed
No. PFC
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI1…DI3: Free
DI4: Speed Reg Motor
DI5…DI6: Free
Not allowed
1
DI1…DI3: Free
DI4: Speed Reg Motor
DI5: First PFC Relay
DI6: Free
DI1…DI3: Free
DI4: First PFC Relay
DI5…DI6: Free
2
DI1…DI3: Free
DI4: Speed Reg Motor
DI5: First PFC Relay
DI6: Second PFC Relay
DI1…DI3: Free
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Free
3 Not allowed
DI1…DI3: Free
DI4: First PFC Relay
DI5: Second PFC Relay
DI6: Third PFC Relay
4…6 Not allowed Not allowed

Table of Contents