Parameters 211
Enabled (init at stop
/power-up)
When enabled, the motor potentiometer first adopts the value
defined by parameter 22.72 Motor potentiometer initial value.
The value can then be adjusted from the up and down
sources defined by parameters 22.73 Motor potentiometer up
source and 22.74 Motor potentiometer down source.
A stop or a power cycle will reset the motor potentiometer to
the initial value (22.72).
1
Enabled (resume
always)
As Enabled (init at stop /power-up), but the motor
potentiometer value is retained over a power cycle.
2
Enabled (init to
actual)
Whenever another reference source is selected, the value of
the motor potentiometer follows that reference. After the
source of reference returns to the motor potentiometer, its
value can again be changed by the up and down sources
(defined by 22.73 and 22.74).
3
22.72 Motor
potentiometer initial
value
Defines an initial value (starting point) for the motor
potentiometer. See the selections of parameter 22.71 Motor
potentiometer function.
0.00
-32768.00…
32767.00
Initial value for motor potentiometer. 1 = 1
22.73 Motor
potentiometer up
source
Selects the source of motor potentiometer up signal.
0 = No change
1 = Increase motor potentiometer value. (If both the up and
down sources are on, the potentiometer value will not
change.)
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 7…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page
255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Reserved 21…23
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 24
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 25
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 26
Other [bit] Source selection (see Terms and abbreviations on page 144). -
22.74 Motor
potentiometer down
source
Selects the source of motor potentiometer down signal.
0 = No change
1 = Decrease motor potentiometer value. (If both the up and
down sources are on, the potentiometer value will not
change.)
For the selections, see parameter 22.73 Motor potentiometer
up source.
Not selected
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 211 Wednesday, September 21, 2016 9:48 PM