Parameters 179
06.101 User control word 2 User-defined control word 2. -
0000h…FFFFh User-defined control word 2. 1 = 1
06.116 LSU drive status
word 1
(Only visible when IGBT supply unit control activated by
95.20)
Drive status word 1 received from the supply unit.
See also section Control of a supply unit (LSU) (page 77),
and parameter group 60 DDCS communication.
This parameter is read-only.
-
0000h…FFFFh Drive status word 1. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 User control word 2 bit 0 User-defined bit.
1 User control word 2 bit 1 User-defined bit.
…… …
15 User control word 2 bit 15 User-defined bit.
Bit Name Description
0 Enabled 1 = Run enable and start enable signals are present
1 Inhibited 1 = Start inhibited
2 Operation
allowed
1 = Drive is ready to operate
3 Ready to start 1 = Drive is ready to receive a start command
4 Running 1 = Drive is ready to follow given reference
5 Started 1 = Drive has been started
6 Modulating 1 = Drive is modulating (output stage is being controlled)
7 Limiting 1 = Any operating limit is active
8 Local control 1 = Drive is in local control
9Network
control
1 = Drive is in network control
10 Ext1 active 1 = Control location Ext1 active
11 Ext2 active 1 = Control location Ext2 active
12 Charging relay 1 = Charging relay is closed
13 MCB relay 1 = MCB relay is closed
14…15 Reserved