Parameters 289
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 148). -
28.23 Constant frequency
sel2
When bit 0 of parameter 28.21 Constant frequency function is
0 (Separate), selects a source that activates constant
frequency 2.
When bit 0 of parameter 28.21 Constant frequency function is
1 (Packed), this parameter and parameters 28.22 Constant
frequency sel1 and 28.24 Constant frequency sel3 select
three sources that are used to activate constant frequencies.
See table at parameter 28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant frequency
sel1.
Not selected
28.24 Constant frequency
sel3
When bit 0 of parameter 28.21 Constant frequency function is
0 (Separate), selects a source that activates constant
frequency 3.
When bit 0 of parameter 28.21 Constant frequency function is
1 (Packed), this parameter and parameters 28.22 Constant
frequency sel1 and 28.23 Constant frequency sel2 select
three sources that are used to activate constant frequencies.
See table at parameter 28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant frequency
sel1.
Not selected
28.26 Constant frequency
1
Defines constant frequency 1 (the frequency the motor will
turn when constant frequency 1 is selected).
0.00 Hz
-500.00 … 500.00
Hz
Constant frequency 1. See par.
46.02
28.27 Constant frequency
2
Defines constant frequency 2. 0.00 Hz
-500.00 … 500.00
Hz
Constant frequency 2. See par.
46.02
28.28 Constant frequency
3
Defines constant frequency 3. 0.00 Hz
-500.00 … 500.00
Hz
Constant frequency 3. See par.
46.02
28.29 Constant frequency
4
Defines constant frequency 4. 0.00 Hz
-500.00 … 500.00
Hz
Constant frequency 4. See par.
46.02
28.30 Constant frequency
5
Defines constant frequency 5. 0.00 Hz
-500.00 … 500.00
Hz
Constant frequency 5. See par.
46.02
28.31 Constant frequency
6
Defines constant frequency 6. 0.00 Hz
-500.00 … 500.00
Hz
Constant frequency 6. See par.
46.02
No. Name/Value Description Def/FbEq16