290 Parameters
28.32 Constant frequency
7
Defines constant frequency 7. 0.00 Hz
-500.00 … 500.00
Hz
Constant frequency 7. See par.
46.02
28.41 Frequency ref safe Defines a safe frequency reference value that is used with
supervision functions such as
• 12.03 AI supervision function
• 49.05 Communication loss action
• 50.02 FBA A comm loss func
• 50.32 FBA B comm loss func
• 58.14 Communication loss action.
0.00 Hz
-500.00 … 500.00
Hz
Safe frequency reference. See par.
46.02
28.51 Critical frequency
function
Enables/disables the critical frequencies function. Also
determines whether the specified ranges are effective in both
rotating directions or not.
See also section Critical speeds/frequencies (page 80).
0000b
0000b…0011b Critical frequencies configuration word. 1 = 1
28.52 Critical frequency 1
low
Defines the low limit for critical frequency 1.
Note: This value must be less than or equal to the value of
28.53 Critical frequency 1 high.
0.00 Hz
-500.00 … 500.00
Hz
Low limit for critical frequency 1. See par.
46.02
28.53 Critical frequency 1
high
Defines the high limit for critical frequency 1.
Note: This value must be greater than or equal to the value of
28.52 Critical frequency 1 low.
0.00 Hz
-500.00 … 500.00
Hz
High limit for critical frequency 1. See par.
46.02
28.54 Critical frequency 2
low
Defines the low limit for critical frequency 2.
Note: This value must be less than or equal to the value of
28.55 Critical frequency 2 high.
0.00 Hz
-500.00 … 500.00
Hz
Low limit for critical frequency 2. See par.
46.02
28.55 Critical frequency 2
high
Defines the high limit for critical frequency 2.
Note: This value must be greater than or equal to the value of
28.54 Critical frequency 2 low.
0.00 Hz
-500.00 … 500.00
Hz
High limit for critical frequency 2. See par.
46.02
No. Name/Value Description Def/FbEq16
Bit Name Information
0 Enable 1 = Enable: Critical frequencies enabled.
0 = Disable: Critical frequencies disabled.
1 Sign mode 1 = According to par: The signs of parameters 28.52…28.57 are taken
into account.
0 = Absolute: Parameters 28.52…28.57 are handled as absolute values.
Each range is effective in both directions of rotation.