448 Parameters
0.00...32000.00 Downthrust head 1. 10 = 1
85.13 Downthrust flowrate
1
Defines curve 1 Flow value for the Downthrust limit. 0.00
0.00...32000.00 Downthrust flowrate 1. 10 = 1
85.14 Upthrust head 1 Defines curve 1 Head value for the Upthrust limit. 0.00
0.00...32000.00 Upthrust head 1. 10 = 1
85.15 Upthrust flowrate 1 Defines curve 1 Flow value for the Upthrust limit. 0.00
0.00...32000.00 Upthrust flowrate. 10 = 1
85.16 DNT zone 50%
Head 1
Defines curve 1 Head value at the corresponding Flow value
of 1/2 of the Downthrust zone, i.e. Head point at 1/2 of Flow
interval 0 and parameter 85.13 Downthrust flowrate 1.
0.00
0.00...32000.00 DNT zone 50% head 1. 10 = 1
85.17 UPT zone 50%
Head 1
Defines curve 1 Head value at the corresponding Flow value
of 1/2 of the Upthrust zone, i.e. Head point at 1/2 of Flow
interval. See parameters 85.11 Flowrate max 1 and 85.15
Upthrust flowrate 1.
0.00
0.00...32000.00 UPT zone 50% head 1. 10 = 1
85.18 Workzone 1/3 Head
1
Defines curve 1 Head value at the corresponding Flow value
of 1/3 of the Work zone, i.e Head point at 1/3 of Flow interval.
See parameters 85.13 Downthrust flowrate 1 and 85.15
Upthrust flowrate 1.
0.00
0.00...32000.00 Workzone 1/3 head 1. 10 = 1
85.19 Workzone 2/3 Head
1
Defines curve 1 Head value at the corresponding Flow value
of 2/3 of the Work zone, i.e Head point at 2/3 of Flow interval.
See parameters 85.13 Downthrust flowrate 1 and 85.15
Upthrust flowrate 1.
0.00
0.00...32000.00 Workzone 2/3 head 1. 10 = 1
85.20 Head at 0 flowrate 2 See parameter 85.10 Head at 0 flowrate 1 (page 447). 0.00
85.21 Flowrate max 2 See parameter 85.11 Flowrate max 1 (page 447). 0.00
85.22 Downthrust head 2 See parameter 85.12 Downthrust head 1 (page 447). 0.00
85.23 Downthrust flowrate
2
See parameter 85.13 Downthrust flowrate 1 (page 448). 0.00
85.24 Upthrust head 2 See parameter
85.14 Upthrust head 1 (page 448). 0.00
85.25 Upthrust flowrate 2 See parameter 85.15 Upthrust flowrate 1 (page 448). 0.00
85.26 DNT zone 50%
Head 2
See parameter 85.16 DNT zone 50% Head 1 (page 448). 0.00
85.27 UPT zone 50%
Head 2
See parameter 85.17 UPT zone 50% Head 1 (page 448). 0.00
85.28 Workzone 1/3 Head
2
See parameter 85.18 Workzone 1/3 Head 1 (page 448). 0.00
85.29 Workzone 2/3 Head
2
See parameter 85.19 Workzone 2/3 Head 1 (page 448). 0.00
85.30 Head at 0 flowrate 3 See parameter 85.10 Head at 0 flowrate 1 (page 447). 0.00
85.31 Flowrate max 3 See parameter 85.11 Flowrate max 1 (page 447). 0.00
85.32 Downthrust head 3 See parameter 85.12 Downthrust head 1 (page 447). 0.00
85.33 Downthrust flowrate
3
See parameter 85.13 Downthrust flowrate 1 (page 448). 0.00
No. Name/Value Description Def/FbEq16