Parameters 447
NULL Zero 0
AI1 scaled See parameter 12.12 AI1 scaled value (see page 197). 1
AI2 scaled See parameter 12.22 AI2 scaled value (see page 199). 2
FBA1 ref See parameter 03.05 FB A reference 1 (page 156). 3
FBA2 ref See parameter 03.06 FB A reference 2 (page 156). 4
EFB1 ref See parameter 03.09 EFB reference 1 (page 156). 5
EFB2 ref See parameter 03.10 EFB reference 2 (page 156). 6
Aux input data 1 Value set in parameter 85.71 Aux input data 1.7
Aux input data 2 Value set in parameter 85.71 Aux input data 2.8
Other Source selection (see Terms and abbreviations on page 148). -
85.03 Input 2 source Defines source 2 for signal that can be used as an input for
the pump curve function.
For parameter selections, see parameter 85.02 Input 1
source.
Aux input
data 2
85.04 Curve frequency 1 Defines Q-H pump curve frequency 1.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz Curve frequency in Hz. 10 = 1Hz
85.05 Curve frequency 2 Defines Q-H pump curve frequency 2.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz Curve frequency in Hz. 10 = 1Hz
85.06 Curve frequency 3 Defines Q-H pump curve frequency 3.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz Curve frequency in Hz. 10 = 1Hz
85.07 Curve frequency 4 Defines Q-H pump curve frequency 4.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz Curve frequency in Hz. 10 = 1Hz
85.08 Curve frequency 5 Defines Q-H pump curve frequency 5.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz Curve frequency in Hz. 10 = 1Hz
85.09 Pump curve scale
coef
Defines scale coefficient for the Q-H pump curves.
Typically, the pump manufacturers specify Q-H curves valid
for water. Set the value corresponding to a specific gravity of
the pumped fluid.
1.000
0.000...30.000 Pump curve scale coef. 1000 = 1
85.10 Head at 0 flowrate 1 Defines curve 1 maximum Head value at the corresponding
Flow value of 0.
0.00
0.00...32000.00 Head at 0 flowrate 1. 10 = 1
85.11 Flowrate max 1 Defines curve 1 maximum Flow value at the corresponding
Head value of 0.
0.00
0.00...32000.00 Maximum flowrate. 10 = 1
85.12 Downthrust head 1 Defines curve 1 Head value for the Downthrust limit. 0.00
No. Name/Value Description Def/FbEq16