Parameters 461
91.02 Module 1 status Displays the type of the interface module found in the location
specified by parameter 91.12 Module 1 location.
This parameter is read-only.
-
No option No module detected in the specified slot. 0
No communication A module has been detected but cannot be communicated
with.
1
Unknown The module type is unknown. 2
FEN-01 An FEN-01 module has been detected and is active. 16
FEN-11 An FEN-11 module has been detected and is active. 17
FEN-21 An FEN-21 module has been detected and is active. 18
FEN-31 An FEN-31 module has been detected and is active. 21
FSE-31 An FSE-31 module has been detected and is active. 25
91.03 Module 2 status Displays the type of the interface module found in the location
specified by parameter 91.14 Module 2 location.
For the indications, see parameter 91.02 Module 1 status.
This parameter is read-only.
-
91.04 Module 1
temperature
Displays the temperature measured through the sensor input
of interface module 1. The unit is selected by parameter
96.16 Unit selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
0…1000 °C, °F or
ohm
Temperature measured through interface module 1. -
91.06 Module 2
temperature
Displays the temperature measured through the sensor input
of interface module 2. The unit is selected by parameter
96.16 Unit selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
0…1000 °C, °F or
ohm
Temperature measured through interface module 2. -
91.10 Encoder parameter
refresh
Validates any changed encoder interface module parameters.
This is needed for any parameter changes in groups 90…93
to take effect.
After refreshing, the value reverts automatically to Done.
Notes:
• Permanent magnet motors only: The drive will perform a
fresh autophasing routine (see page 96) at next start if the
motor feedback encoder settings have been changed.
• The parameter cannot be changed while the drive is
running.
Done
Done Refreshing done. 0
Refresh Refreshing. 1
91.11 Module 1 type Defines the type of the module used as interface module 1. None
None None (communication disabled). 0
FEN-01 FEN-01. 1
FEN-11 FEN-11. 2
FEN-21 FEN-21. 3
FEN-31 FEN-31. 4
No. Name/Value Description Def/FbEq16