462 Parameters
FSE-31 FSE-31. 5
91.12 Module 1 location Specifies the slot (1…3) on the control unit of the drive into
which the interface module is installed. Alternatively, specifies
the node ID of the slot on an FEA-03 extension adapter.
Slot 2
Slot 1 Slot 1. 1
Slot 2 Slot 2. 2
Slot 3 Slot 3. 3
4…254 Node ID of the slot on the FEA-03 extension adapter. 1 = 1
91.13 Module 2 type Defines the type of the module used as interface module 2. None
None None (communication disabled). 0
FEN-01 FEN-01. 1
FEN-11 FEN-11. 2
FEN-21 FEN-21. 3
FEN-31 FEN-31. 4
FSE-31 FSE-31. 5
91.14 Module 2 location Specifies the slot (1…3) on the control unit of the drive into
which the interface module is installed. Alternatively, specifies
the node ID of the slot on an FEA-03 extension adapter.
Slot 3
Slot 1 Slot 1. 1
Slot 2 Slot 2. 2
Slot 3 Slot 3. 3
4…254 Node ID of the slot on the FEA-03 extension adapter. 1 = 1
91.21 Module 1 temp
sensor type
Specifies the type of temperature sensor connected to
interface module 1. Note that the module must also be
activated by parameters 91.1191.12.
None
None None. 0
PTC PTC. (The unit is ohms.) 1
KTY-84 KTY84. (The unit is selected by parameter 96.16 Unit
selection.)
2
91.22 Module 1 temp filter
time
Defines a filtering time for the temperature measurement
through interface module 1.
1500 ms
0…10000 ms Filtering time for temperature measurement. -
91.24 Module 2 temp
sensor type
Specifies the type of temperature sensor connected to
interface module 2. Note that the module must also be
activated by parameters 91.1391.14.
None
None None. 0
PTC PTC. (The unit is ohms.) 1
KTY-84 KTY84. (The unit is selected by parameter 96.16 Unit
selection.)
2
91.25 Module 2 temp filter
time
Defines a filtering time for the temperature measurement
through interface 2.
1500 ms
0…10000 ms Filtering time for temperature measurement. -
91.31 Module 1 TTL
output source
Selects the encoder input on interface module 1 whose signal
is echoed by or emulated to the TTL output.
See also section Encoder support (page 86).
Not selected
Not selected TTL output not in use. 0
No. Name/Value Description Def/FbEq16