594 Fault tracing
6181 FPGA version
incompatible
Firmware and FPGA file
version in the power unit are
incompatible.
Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Update of power unit logic
failed.
Retry.
6200 Checksum mismatch
Programmable fault: 96.54
Checksum action
The calculated parameter
checksum does not match any
enabled reference checksum.
See A686 Checksum mismatch (page
574).
6306 FBA A mapping file Fieldbus adapter A mapping
file read error.
Contact your local ABB representative.
6307 FBA B mapping file Fieldbus adapter B mapping
file read error.
Contact your local ABB representative.
6481 Task overload Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
6487 Stack overflow Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A1 Internal file load File read error. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A2 Internal record load Internal record load error. Contact your local ABB representative.
64A3 Application loading Application file incompatible or
corrupted.
Check the auxiliary code. See actions for
each code below.
8006 Not enough memory for the
application.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
8007 The application contains the
wrong system library version.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
8008 The application is empty. In Automation Builder, give a “Clean
command and reload the application.
8009 The application contains
invalid tasks.
In Automation Builder, check application
task configuration, give a “Clean all
command, and reload the application.
800A The application contains an
unknown target (system)
library function.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
64A5 Licensing fault Running the control program is
prevented either because a
restrictive license exists, or
because a required license is
missing.
Record the auxiliary codes of all active
licensing faults and contact your product
vendor for further instructions.
Code
(hex)
Fault Cause What to do