Fault tracing 595
64A6 Adaptive program Error running the adaptive
program.
Check the auxiliary code (format
XXXX YYYY). “XXXX” specifies the
number of the function block (0000 =
generic error). “YYYY” indicates the
problem (see actions for each code
below).
000A Program corrupted or block
non-existent
Restore the template program or
download the program to the drive.
000C Required block input missing Check the inputs of the block.
000E Program corrupted or block
non-existent
Restore the template program or
download the program to the drive.
0011 Program too large. Remove blocks until the error stops.
0012 Program is empty. Correct the program and download it to
the drive.
001C A nonexisting parameter or
block is used in the program.
Edit the program to correct the parameter
reference, or to use an existing block.
001D Parameter type invalid for
selected pin.
Edit the program to correct the parameter
reference.
001E Output to parameter failed
because the parameter was
write-protected.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
0023 Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
0024
002A Too many blocks. Edit the program to reduce the number of
blocks.
Other Contact your local ABB representative,
quoting the auxiliary code.
64B0 Memory unit detached The memory unit was
detached when the control unit
was powered.
Switch off the power to the control unit
and reinstall the memory unit.
In case the memory unit was not actually
removed when the fault occurred, check
that the memory unit is properly inserted
into its connector and its mounting screw
is tight. Reboot the control unit (using
parameter 96.08 Control board boot) or
by cycling power. If the problem persists,
contact your local ABB representative.
64B1 Internal SSW fault Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
64B2 User set fault Loading of user parameter set
failed because
requested set does not exist
set is not compatible with
control program
drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
Code
(hex)
Fault Cause What to do