Notes:
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5
2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
1)
Current [0(4)…20 mA, R
in
= 100 ohm] or voltage [0(2)…10 V, R
in
> 200 kohm] input
selected by switch AI2. Change of setting requires reboot of control unit.
2)
Current [0(4)…20 mA, R
in
= 100 ohm] or voltage [0(2)…10 V, R
in
> 200 kohm] input
selected by switch AI1. Change of setting requires reboot of control unit.
3)
See section The XD2D connector (page 51).
4)
See chapter The Safe torque off function (page 183).
5)
Constant speed 1 is defined by parameter 22.26.
6)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use. 1 =
Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
7)
Determines whether DICOM is separated from DIOGND (ie. common reference for digital
inputs floats; in practice, selects whether the digital inputs are used in current sinking or
sourcing mode). See also ZCU-1x ground isolation diagram (page 56). DICOM=DIOGND
ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate.
8)
See section DIIL input (page 50).
9)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.