Input power (DC) connection
ACS880-107-xxxxx-3: 513…566 V DC. This is indicated in the type designation
label as typical input voltage level (566 V DC).
Voltage (U
1
)
ACS880-107-xxxxx-5: 513…707 V DC. This is indicated in the type designation
label as typical input voltage levels (566/679/707 V DC).
ACS880-107-xxxxx-7: 709…976 V DC. This is indicated in the type designation
label as typical input voltage levels (742/849/976 V DC).
TN (grounded) and IT (ungrounded) systems up to 690 V AC, corner-grounded
systems up to 600 V AC
Drive AC supply network
type
Motor (AC) connection
Asynchronous AC induction motors, permanent magnet synchronous motors and
AC induction servomotors
Motor types
3-phase symmetrical, Umax at field weakening point:Voltage (U
2
)
ACS880-107-xxxxx-3: 0…400 V AC. The maximum value (400 V) is a typical drive
input voltage level shown on the type designation label of the supply unit corres-
ponding to 380…415 V AC.
ACS880-107-xxxxx-5: 0…400/480/500 V AC. The maximum values (400/480/500
V) are typical drive input voltage levels shown on the type designation label of the
supply unit corresponding to 380…500 V AC.
ACS880-107-xxxxx-7: 0…525/600/690 V AC. The maximum values (525/600/690
V) are typical drive input voltage levels shown on the type designation label of the
supply unit corresponding to 525…690 V AC.
0…500 Hz, exceptFrequency (f
2
)
0…120 Hz with sine output filters (option +E206)
0…120 Hz for frames R1i…R5i with du/dt filters (option +E205)
0…200 Hz for frames R6i and R7i with du/dt filters (option +E205)
• For higher operational output frequencies, please contact your local ABB repres-
entative.
• Operation above 150 Hz may require type-specific derating. For more information,
contact your local ABB representative.
See the technical data.Current
Frames R1i…R4i: 4.5 kHz (typical)Switching frequency
Frames R5i…R8i: 3 kHz (typical)
The switching frequency can vary per frame and voltage. For exact values, please
contact your local ABB representative.
*Frames R1i…R2i: 150 m (492 ft)Maximum recommended
motor cable length
*Frames R3i…R7i: 300 m (984 ft)
Frame R8i and multiples: 500 m (1640 ft)
*Tested with 100 m (328 ft) for EMC Category C3. See standards and markings
information in Electrical planning instructions for ACS880 multidrive cabinets and
modules (3AUA0000102324 [English]).
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and characteristics.
Contact ABB for more information. Note that a sine filter (optional) at the drive
output also causes a voltage decrease.
144 Technical data