Technical data 127
User interface and communication
Environmental
Inverter type PRO-33.0-TL-OUTD-[-/S/SX]-400
Control unit type PVS-AP-L graphical display, detachable
Control unit communication ABB control unit protocol over EIA-485
Remote monitoring communication Modbus RTU protocol over EIA-485 or
ABB control unit protocol over EIA-485
Remote monitoring adapter type VSN700-03/-05 data logger (optional)
Electrically isolated relay output with FIO-01 accessory
PV plant sensor connection with FIO-11 accessory
Inverter type PRO-33.0-TL-OUTD-[-/S/SX]-400
Environmental category Outdoor, avoid installation subject to direct sunlight or
rainwater
Ingress protection class IP65/IP54 monitored fans
Ingress protection class with first
cover open
IP20
Pollution degree class PD3
Ambient temperature range allowed
during operation
-25
+60 °C (-13+140 °F)
Maximum ambient temperature for
nominal power output
+4C (+11F)
Output current decreases according to the
temperature rise rate in the inverter
Ambient temperature range allowed
during storage and transportation
-40
+70 °C (-40+158 °F)
Relative humidity level allowed, not
condensing
0...100%
Maximum installation altitude above
sea level
3,000 m (9840 ft)
Above 1,000 m (3280 ft), the maximum power derating
depends on the ambient temperature
Minimum installation clearances
(Top/Sides/Bottom)
250/350/500 mm
(9.8 in./13.8 in./19.7 in.)
Noise emissions (at the operator’s
position):
Values determined according to standards IEC 62109-
1, ISO4871 and the noise test code in ISO3746.
The declared noise emission values are the sum of the
measured values and the associated uncertainty. They
represent the upper boundaries of the range which is
likely to occur in measurements. The measurement
distance was 1 m and the operating conditions applied
to each inverter were: 580 V
DC
, 400 V
AC
, 50 Hz,
nominal power output, fans running.
A-weighted sound power level 67 dBA