40.13 Pre PID frequency
0: Disable Pre PID function
Range: 0.00 ~ 400.0 Hz in 0.01 Hz
Initial value: 0.00 Hz
Program the frequency reference when PID function is activated. Once the VFD frequency
out reaches this value in
'40.13' (Pre PID frequency)
PID control function is enabled and the
VFD is operated in closed loop control.
Run command
01.01 (Output Frequency)
40.17 (PID feedback)
PID operation
ON
ON
40.13 (Pre PID frequency)
40.02 (PID reference)
40.14 PID sleep frequency
Range: 0.00 ~ 400.0 Hz in 0.01 Hz
Initial value: 0.00 Hz
Program the frequency reference when the VFD goes sleep
40.18 (PID output)
Motor status
Run
ON
40.14 (PID Sleep reference)
40.16 (PID Wake Up frequency)
Stop
40.15 (Sleep/Wake up
Delay time)
Run command
Run
01.01 (Output Frequency)
40.15 PID sleep/wake delay time
Range: 0.0 ~ 30.0 Sec in 0.1 Sec
Initial value: 0.0 Sec
Program the frequency reference when the VFD goes sleep